| Central Lighting Inverter
|
 |
FEATURES
 |
Single Phase
|
 |
500 - 3000 VA
|
 |
HID, Incandescent, Fluorescent
|
 |
U.L. 924,
924A
Listed
|
 |
Small Footprint, Lightweight
|
 |
Sine Wave Output
|
 |
Front access and Easy Installation
|
|
STANDARD FEATURES
Low Profile Compact Cabinet
Single Phase, Full Range Voltage Regulation
AC Power ON Indicator
Battery ON Indicator
Charger ON Indicator
DC Battery Switch
AC Line Switch |
|
SPECIFICATIONS
|
 |
| Sizes: |
 |
500, 1250, 1500, 2000,
and 3000
|
 |
| Input Voltage: |
|
120 Volt Only +10% On-Line zero Transfer time,
277 Volt Input with external Isolation Transformer Only
|
 |
| Output Voltage: |
|
120 Volt Only, or 277 Volt with external Isolation Transformer Only
|
 |
| Output Frequency: |
|
60 Hz. +5%
|
 |
| Output Voltage Reg.: |
|
+4% for all loads and for Battery Discharge mode
|
 |
| Output Wave Form: |
|
Sinewave during emergency a 10% max. THD with linear load
|
 |
| Output Protection: |
|
Current limiting and short circuit protection
|
 |
| Efficiency: |
|
70% minimum @ normal mode
|
 |
| Battery: |
|
Maintenance free sealed lead calcium
|
|
|
48 VDC for 500, 750, & 1000 VA
72 VDC for 1250, 1500, & 2000 VA
|
 |
| Recharge Time: |
|
Recharge Time per U.L. 924
|
 |
| Environmental: |
|
Humidity: 0 - 95% RH w/no condensation
|
|
|
Operating Temp.:
UPS: 0°C to +40°C. (-32°F to 102°F)
Battery: 20°C to +30°C.
(68°F to 86°F)
|
 |
External
Isolation
Transformer
Isolation Transformers must be used on all input or output voltages other than 120. By using the Isolation Transformer, you have the choice of 208 or 240 or 277 Volts on the input or output.
Note, these are all externally mounted.
|
|
|
|
500, 750, 1000, 1250
VA |
2000-3000 VA |
|
 |

|
|
|