FEATURES

Caltrans approved
2 Hours of full run with programmed
flash signal
Shelf or Rack mountable
Fits inside a Caltrans 332 cabinet
Manual bypass switch external to unit
Certified for operation from -35C to +74C
Meters for accumulated runtime and event counter
Temperature compensated battery charger
These units can be installed in a companion, attachable, external cabinet

INPUT SPECIFICATION

Nominal Input Voltage120 VAC single phase
Input Voltage Range138 VAC to 85 VAC
Input Frequency60 Hz + 5%
Input Configuration2 wire (hot & neutral)
Input ProtectionSingle pole switch & inline fuse
Transient ProtectionANSI @ 62.41 IEEE 587 (A&B)
OUTPUT SPECIFICATION

Power Rating 1,000 VA / 750 Watts
Nominal Output Voltage120 VAC, 60 Hz single phase
Output Voltage Regulation+2% from no load to full load and from high
battery to low battery
Output Frequency 60 Hz +3Hz, compatible w/all NEMA flasher
Output Wave FormSine wave
Over Load Capability125% for ten (10) minutes.
Fault Condition The unit shall withstand a short circuit on any output
without causing damage to the system. However a single or multiple
sustained short will be fuse cleared within 20 seconds or less.
Efficiency97%
Power Factor Load Capability0.7 leading to unity

PHYSICAL SPECIFICATION

Cabinet Dimension: 19 Wide x 5.1 High x 15 Deep

ENVIRONMENTAL

Operating Temp.: -30F. (-35C.) to 165F. (74C.)
Storage Temp.: -30F. (-35C.) to 165F. (74C.)
Operating Humidity: 0 to 95% Non-Condensing






Data Sheets
Lock-In Specification
Manual